Power Factor Calculator

Power Factor Calculator
PF = cos(θ)
PF = P/S
S = √(P²+Q²)
Qc = P(tanθ₁−tanθ₂)
Enter Known Values
V Voltage (V rms)
I Current (I rms)
PF Power Factor
Enter PF (0-1) or phase angle
f Frequency
Needed for correction capacitor
Enter values to calculate power factor
Power Factor Results
Power Factor
Phase Angle

Power triangle: P (real), Q (reactive), S (apparent)

Power Factor
cos(θ)
Phase θ
degrees
Leading/Lagging
 
Real P
W
Reactive Q
VAR
Apparent S
VA
Size a PF Correction Capacitor

Enter current PF, target PF, real power and frequency.

PF Current PF
PF Target PF
P Real Power
V Supply Voltage
f Frequency
PF Correction Result
Required C
µF
Reactive kVAR
kVAR
Current Reduction
A saved

Power Triangle & PF Correction P (Real, W) Q(Reactive, VAR) S (Apparent, VA) θ Q' (corrected) S' (smaller) Cap bankcancels Q PF = P/S = cos(θ) — Adding capacitance reduces Q, shrinking S and improving PF

Figure 1: The power triangle shows how real power (P), reactive power (Q) and apparent power (S) relate. A correction capacitor cancels reactive power, reducing S and improving PF towards unity.

Table of Contents
Fundamentals
  1. What Is Power Factor?
  2. The Power Triangle
Worked Examples
  1. Industrial Motor
  2. Office Building
  3. Correction Capacitor Sizing
Deep Dive
  1. Why Power Factor Matters
  2. Power Factor Correction Methods
  3. Utility Penalties and Standards
  4. Harmonics and Displacement PF
Reference
  1. Frequently Asked Questions
  2. Related AC Circuit Calculators

What Is Power Factor?

Power factor (PF) is the ratio of real power to apparent power in an AC circuit: PF = P / S = cos(θ). It tells you how efficiently the supply current is being used. A PF of 1.0 means every amp of current delivers useful work. A PF of 0.5 means you need twice the current for the same real power — the extra current generates heat in cables and transformers without doing anything productive.

Power factor arises because inductors and capacitors store and return energy each cycle, creating reactive current that flows back and forth but does no useful work. The Phase Angle Calculator shows the angle between voltage and current that gives rise to this effect.

The Power Triangle

Real Power P = V × I × cos(θ) [watts, W]
Reactive Power Q = V × I × sin(θ) [volt-amps reactive, VAR]
Apparent Power S = V × I [volt-amps, VA]
S = √(P² + Q²) and PF = P / S

The power triangle is a right triangle: P along the horizontal (useful work), Q along the vertical (reactive energy), and S as the hypotenuse (total current demand). The angle between P and S is the phase angle θ.

Worked Example — Industrial Motor

Given: 230V, 10A, PF = 0.7 lagging, 50 Hz

Step 1 — S = 230 × 10 = 2300 VA

Step 2 — P = 2300 × 0.7 = 1610 W

Step 3 — Q = 2300 × sin(45.6°) = 1643 VAR

Step 4 — θ = arccos(0.7) = 45.6°

This motor draws 2.3 kVA from the supply but only delivers 1.61 kW of useful shaft power. The remaining 1.64 kVAR of reactive power heats the wiring without doing work.

Worked Example — Office Building

Given: P = 50 kW, S = 62.5 kVA

Step 1 — PF = 50/62.5 = 0.80

Step 2 — Q = √(62.5² − 50²) = 37.5 kVAR

Step 3 — θ = arccos(0.80) = 36.9°

The building’s PF of 0.80 means the transformer must be rated at 62.5 kVA even though only 50 kW is used. Correcting to PF = 0.95 would allow a 52.6 kVA transformer — a 16% reduction in capacity and cost.

Worked Example — Correction Capacitor Sizing

Given: P = 50 kW, current PF = 0.80, target PF = 0.95, V = 400V, f = 50 Hz

Step 1 — Qc = P(tanθ1 − tanθ2) = 50000(0.75 − 0.329) = 21.1 kVAR

Step 2 — C = Qc / (2πfV²) = 21100 / (314.16 × 160000) = 419.6 µF

A 420 µF capacitor bank at 400V would improve the building’s PF from 0.80 to 0.95. The PF Correction Sizing tab in the calculator above performs this calculation automatically for any input values.

Why Power Factor Matters

Poor power factor increases current demand, which causes higher I²R losses in cables, requires larger transformers and switchgear, and triggers reactive power penalties from electricity suppliers. In the UK, industrial tariffs typically charge for reactive power when PF drops below 0.9. Improving PF from 0.7 to 0.95 reduces supply current by 26% and cable losses by 46%.

Power Factor Correction Methods

The most common method is adding parallel capacitors to cancel the inductive reactive power from motors and transformers. Capacitors can be fixed (for constant loads) or automatically switched (for varying loads). Synchronous condensers and active PFC circuits are used in more specialised applications.

Do not overcorrect. Pushing PF above 0.98 or into leading territory can cause voltage rise, resonance with supply impedance, and protection relay problems. Target 0.95 to 0.98 for safety.

The Impedance Calculator can model how adding correction capacitance changes the circuit’s overall impedance and phase angle.

Utility Penalties and Standards

Most UK electricity distribution codes require a PF above 0.9 for industrial connections. Below this, customers pay a reactive power charge (typically per kVAR per month) or face a maximum demand penalty based on kVA rather than kW. Some European networks require PF > 0.95 for new connections.

Harmonics and Displacement PF

The power factor described above is the displacement power factor — it measures the phase shift at the fundamental frequency. When non-linear loads (like rectifiers and VFDs) generate harmonics, the true power factor is lower because harmonic currents contribute to apparent power without useful work. True PF = displacement PF × distortion factor. The Three Phase Power Calculator handles multi-phase systems where harmonic distortion is a common concern.

Frequently Asked Questions

Can power factor be greater than 1?
No. Power factor ranges from 0 to 1. A PF of 1 means all power is real (purely resistive load). A PF of 0 means all power is reactive (pure inductor or capacitor).
What is the typical PF of a home?
Residential power factor is typically 0.85-0.95, dominated by refrigerator compressors, washing machine motors, and air conditioning. UK domestic tariffs do not currently penalise low PF, but it still wastes energy in house wiring.
Do LED lights have good power factor?
Quality LED drivers have PF > 0.9. Cheap drivers may have PF as low as 0.5. Check the driver specifications — PF is often listed on the datasheet or product label.
What causes leading power factor?
Capacitive loads or over-corrected power factor correction banks. Long unloaded cables also appear capacitive. Leading PF can cause voltage rise and should generally be avoided.
Is power factor the same for single and three phase?
The concept is the same, but three-phase calculations use line or phase values and include a √3 factor. The PF Correction tab works for single-phase; for three-phase sizing use the Three Phase Power Calculator.
How often should PF correction capacitors be checked?
Annually for fixed installations. Capacitors degrade over time (especially in hot environments) and can fail short-circuit. Automatic PFC controllers should have their switching checked and capacitor bank health verified yearly.

Browse all Electronics Calculators →

Last updated: March 2026