Three Phase Power Calculator

Three Phase Power Calculator
P = √3 × VL × IL × PF
VL = √3 × VP (star)
IL = √3 × IP (delta)
Star (Wye) Connection — Enter Line or Phase Values
VL Line Voltage
IL Line Current
PF Power Factor
0 to 1 (default: 1 for resistive)
f Frequency
Enter line voltage and current
Three Phase Power Results
Total Real Power
Total Apparent Power
VLine
V
VPhase
V
ILine
A
IPhase
A
Real P (total)
W
Apparent S (total)
VA
Reactive Q (total)
VAR
Phase Angle θ
degrees
Per-Phase Power
W
Star (Wye) Y Delta Δ A B C N VL = √3 × VP IL = IP ABC VL = VP IL = √3 × IP

Figure 1: In star connection, VL = √3 × VP and IL = IP. In delta connection, VL = VP and IL = √3 × IP. Total power is the same: P = √3 × VL × IL × PF.

Table of Contents
Fundamentals
  1. What Is Three Phase Power?
  2. Star (Wye) vs Delta Connections
  3. Key Formulas
Worked Examples
  1. UK Industrial Motor (400V)
  2. US Commercial Building (480V)
  3. Delta-Connected Heating Load
Deep Dive
  1. Why Three Phase?
  2. Balanced vs Unbalanced Loads
  3. The Role of the Neutral
Reference
  1. Frequently Asked Questions
  2. Related AC Circuit Calculators

What Is Three Phase Power?

Three phase power is an electrical system that uses three alternating current waveforms, each offset by 120°. It is the standard for power generation, transmission, and distribution worldwide because it delivers more power for the same amount of copper, produces a smoother torque in motors, and naturally balances the load across the supply.

The three phases are conventionally labelled A (or R), B (or S), and C (or T). In a balanced system all three carry equal current at equal voltage with 120° phase spacing. The Voltage Phasor Calculator can visualise the three phasors and verify that they sum to zero in a balanced system.

Star (Wye) vs Delta Connections

There are two ways to connect a three-phase load or source:

Star (Wye, Y): Each winding connects between one line and a common neutral point. The line voltage is √3 times the phase voltage, and line current equals phase current. This connection provides a neutral for single-phase loads and is standard for distribution transformers.

Delta (Δ): Each winding connects between two lines, forming a triangle. The line voltage equals the phase voltage, and line current is √3 times the phase current. Delta is common for motor connections and distribution without a neutral.

Key relationships:
Star: VL = √3 × VP, IL = IP
Delta: VL = VP, IL = √3 × IP
Both: Ptotal = √3 × VL × IL × PF

Key Formulas

QuantityFormulaUnit
Total real powerP = √3 × VL × IL × cos(θ)W
Total apparent powerS = √3 × VL × ILVA
Total reactive powerQ = √3 × VL × IL × sin(θ)VAR
Per-phase powerPphase = VP × IP × cos(θ)W
Power factorPF = P / S = cos(θ)

Worked Example — UK Industrial Motor (400V)

Given: Star connection, VL = 400 V, IL = 25 A, PF = 0.85, f = 50 Hz

Step 1 — VP = 400 / √3 = 230.9 V

Step 2 — IP = IL = 25 A (star: line = phase current)

Step 3 — S = √3 × 400 × 25 = 17.32 kVA

Step 4 — P = 17.32 × 0.85 = 14.72 kW

Step 5 — Q = 17.32 × sin(31.8°) = 9.13 kVAR

This is a typical 15 kW (20 HP) induction motor. The 0.85 power factor means reactive power correction could save about 3.5 A per line. The Power Factor Calculator can size the correction capacitors.

Worked Example — US Commercial Building (480V)

Given: Star connection, VL = 480 V, IL = 50 A, PF = 0.80

Step 1 — VP = 480 / √3 = 277.1 V

Step 2 — S = √3 × 480 × 50 = 41.57 kVA

Step 3 — P = 41.57 × 0.80 = 33.26 kW

In the US, 480V three-phase is standard for commercial and light industrial use. The 277V phase voltage is commonly used for fluorescent lighting on the same system.

Worked Example — Delta-Connected Heating Load

Given: Delta connection, VL = 400 V, IL = 30 A, PF = 1.0 (resistive)

Step 1 — VP = VL = 400 V (delta: line = phase voltage)

Step 2 — IP = 30 / √3 = 17.32 A

Step 3 — P = √3 × 400 × 30 × 1.0 = 20.78 kW

With PF = 1.0, all power is real — no reactive component. This is typical for resistive heating elements. Each heater element sees 400V and draws 17.3A.

Why Three Phase?

Three phase power offers several advantages over single phase. It delivers 73% more power using only 50% more conductors (3 wires vs 2). Three-phase motors are simpler, cheaper, self-starting, and produce smoother torque than single-phase equivalents. The instantaneous power in a balanced three-phase system is constant — unlike single-phase where power pulsates at twice the line frequency, causing vibration.

For transmission, three-phase allows higher power transfer per kilogram of copper, reducing infrastructure costs. This is why virtually all power generation and transmission worldwide is three-phase.

Balanced vs Unbalanced Loads

A balanced load draws equal current in all three phases at the same power factor. The neutral current is zero. Most three-phase motors and heaters are balanced. An unbalanced load — common in buildings with single-phase loads distributed across phases — creates neutral current and unequal phase voltages. Severe imbalance can overheat neutral conductors and damage motors.

The neutral carries the imbalance. In a balanced star system the neutral carries zero current. As imbalance increases, neutral current rises. Never disconnect the neutral of a loaded star system — this can cause dangerous overvoltage on the lightly loaded phases.

The Role of the Neutral

In a star (wye) system, the neutral connects the star point of the load to the star point of the supply. It provides a return path for any imbalance between the three phases and establishes the reference voltage for single-phase loads. In a delta system there is no neutral — all loads are connected between pairs of lines.

The Phase Angle Calculator can help analyse the phase relationship between individual loads on different phases.

Frequently Asked Questions

What is the √3 factor?
The factor √3 (≈ 1.732) arises from the 120° phase difference between the three voltages. It is the geometric relationship between line and phase quantities. In star: VL = √3 × VP. In delta: IL = √3 × IP.
Can I convert between star and delta?
Yes. A star-connected load with impedance ZY per phase is equivalent to a delta-connected load with ZΔ = 3 × ZY per phase. The total power drawn from the supply is the same in both cases.
What is the UK three-phase voltage?
UK three-phase supply is 400V line-to-line (230V phase-to-neutral) at 50 Hz. This replaced the older 415V/240V standard in 1995 to harmonise with European voltages.
How do I measure three-phase power?
Use the two-wattmeter method (works for any balanced or unbalanced load) or a three-phase power analyser. For balanced loads, measure one phase and multiply by 3. The total power P = √3 × VL × IL × PF.
What happens if one phase is lost?
A three-phase motor running on two phases (single-phasing) draws much higher current on the remaining phases, overheats rapidly, and will burn out without protection. Phase-loss relays should be fitted to all three-phase motor installations.
Can I use this calculator for generators?
Yes. The same formulas apply to generators. Enter the generator’s rated voltage, current and power factor to find the total real and apparent power output.

Browse all Electronics Calculators →

Last updated: March 2026