Voltage (orange) and current (blue) phasors with phase angle θ
Figure 1: In inductive circuits voltage leads current (positive θ). In capacitive circuits current leads voltage (negative θ). At resonance θ = 0°.
Enter the target phase angle and one known value — the calculator finds the other.
Table of Contents
What Is Phase Angle?
In an AC circuit the voltage and current do not necessarily peak at the same instant. Phase angle (θ) measures how far apart they are in time, expressed as an angle from 0° to ±90°. When θ = 0° the two waveforms are perfectly aligned and all the power delivered does useful work. As θ moves towards ±90° more of the power is reactive — stored and returned each cycle without doing anything useful.
Phase angle arises because inductors cause current to lag behind voltage, while capacitors cause current to lead voltage. In a circuit with both, the net phase angle depends on which effect dominates at the operating frequency. The Impedance Calculator shows the full complex impedance; this calculator focuses specifically on the angle and its practical consequences for power delivery.
The Phase Angle Formula
Where X = XL − XC (net reactance), R = resistance.
XL = 2πfL, XC = 1/(2πfC).
Power factor: PF = cos(θ)
When X is positive (inductive dominates) the angle is positive and voltage leads current. When X is negative (capacitive dominates) the angle is negative and current leads voltage. At resonance X = 0, θ = 0°, PF = 1.
Worked Example — Inductive Motor at 50 Hz
Step 1 — XL = 2π × 50 × 0.05 = 15.71 Ω
Step 2 — θ = arctan(15.71/15) = 46.3°
Step 3 — PF = cos(46.3°) = 0.691 lagging
A power factor of 0.691 means this motor draws 45% more current than an equivalent resistive load at the same real power. Electricity suppliers penalise industrial customers with a PF below 0.9, making power factor correction essential.
Worked Example — RC Circuit at 1 kHz
Step 1 — XC = 1/(2π × 1000 × 100×10−9) = 1591.5 Ω
Step 2 — θ = arctan(−1591.5/1000) = −57.9°
Step 3 — PF = cos(−57.9°) = 0.531 leading
The large negative angle tells us that at 1 kHz this RC circuit is heavily capacitive. The Capacitive Reactance Calculator can show how XC changes as you sweep the frequency.
Worked Example — RLC at Resonance
Step 1 — XL = 2π × 223.6 × 0.05 = 70.24 Ω
Step 2 — XC = 1/(2π × 223.6 × 10.13×10−6) = 70.24 Ω
Step 3 — X = 70.24 − 70.24 = 0 Ω
Step 4 — θ = arctan(0/100) = 0°, PF = 1.000
At resonance the inductive and capacitive reactances cancel perfectly, leaving pure resistance. This is the principle behind the Resonant Frequency Calculator and is exploited in radio tuning, bandpass filters, and impedance matching networks.
Worked Example — Power Factor Correction
Step 1 — θ = arccos(0.7) = 45.6°
Step 2 — Apparent power S = 230 × 5 = 1150 VA
Step 3 — Real power P = 1150 × 0.7 = 805 W
Step 4 — Reactive power Q = 1150 × sin(45.6°) = 821 VAR
Step 5 — Correction capacitor: C = Q/(2πfV²) = 821/(2π × 50 × 230²) = 49.4 µF
Adding a 50 µF capacitor in parallel brings the power factor to unity. The motor still draws the same real power, but the supply current drops from 5 A to 3.5 A, reducing cable losses and electricity penalties. The Power Factor Calculator provides detailed correction sizing.
Reading the Phasor Diagram
A phasor diagram represents AC quantities as rotating vectors. In this calculator, the current phasor (I) is drawn along the positive horizontal axis as the reference. The voltage phasor (V) is drawn at angle θ above (inductive) or below (capacitive) the current.
The horizontal projection of V onto I represents the resistive (real) component, and the vertical projection represents the reactive (imaginary) component. The longer the vertical projection relative to the horizontal, the worse the power factor.
Power Factor Explained
Power factor (PF) is the ratio of real power to apparent power: PF = P/S = cos(θ). A PF of 1 means every amp of current does useful work. A PF of 0.5 means you need twice the current to deliver the same real power, which doubles the I²R losses in cables and transformers.
UK electricity suppliers typically require a PF above 0.9 for industrial loads. Below that, reactive power charges apply. Residential customers are not penalised directly, but a low PF still wastes energy in the home wiring.
Power Factor Correction
Most real-world loads are inductive (motors, transformers, fluorescent lighting), so PF correction usually means adding parallel capacitors. The capacitor supplies the reactive current locally, reducing the reactive current drawn from the supply.
The correction capacitor value is: C = Qreactive / (2πf V²). Overcorrection (adding too much capacitance) flips the phase angle to leading, which can cause voltage rise and resonance problems. Always target PF = 0.95 to 0.98 rather than exactly 1.0.
Leading vs Lagging
The terms “leading” and “lagging” describe the current relative to the voltage. In an inductive circuit the current lags behind the voltage (lagging PF). In a capacitive circuit the current leads the voltage (leading PF). At resonance the two are in phase and the power factor is unity.
This distinction matters for the Three Phase Power Calculator where leading and lagging loads on different phases can partially cancel each other, and for generator synchronisation where the phase angle determines whether a generator exports or absorbs reactive power.
Frequently Asked Questions
What is the phase angle range?
Is phase angle the same as power factor angle?
Can phase angle be exactly 90°?
How do I measure phase angle?
Does phase angle change with frequency?
Why does my electricity bill mention power factor?
What is the difference between real, reactive and apparent power?
Can I use this calculator for three-phase systems?
Related AC Circuit Calculators
Browse all Electronics Calculators →