Power Triangle Calculator

Power Triangle Calculator – Real, Reactive & Apparent Power
Real, Reactive & Apparent Power
P Real Power (watts)
Q Reactive Power (VAR)
Power Triangle Analysis
Apparent Power (S)
VA
Real Power (P)
Watts
Reactive Power (Q)
VAR
Power Factor
cosθ
Phase Angle (θ)
Load Type

The Power Triangle

In AC circuits, the apparent power (S) is the hypotenuse of a right triangle. The horizontal leg is real power (P) — the power that does useful work. The vertical leg is reactive power (Q) — the power that sloshes back and forth between source and load without doing work.

P (Real Power) Watts (W) — does useful work Q (Reactive) VAR S (Apparent) VA θ S² = P² + Q²   |   PF = P/S = cos(θ) +Q = inductive (lagging)    −Q = capacitive (leading)
P (Real Power) — Watts. The power that does actual work (heat, motion, light). This is what you pay for.
Q (Reactive Power) — VAR. Energy stored and returned by inductors/capacitors each cycle. Does no work but increases current.
S (Apparent Power) — VA. The total power the supply must deliver: S = V × I. Sizes cables and transformers.
θ (Phase Angle) — Angle between voltage and current. PF = cos(θ). Unity PF (θ = 0°) means all power is real.

Power Triangle Calculator

In AC circuits, current and voltage fall out of phase. Power splits into two components: real power (does useful work) and reactive power (sloshes back and forth doing nothing). Apparent power is the vector sum — what the supply must deliver and what sizes cables, transformers, and switchgear. These three form a right triangle. The angle between apparent and real power is the phase angle θ, and cos(θ) is the power factor. Enter any two known values — the calculator solves for everything else.

Core Formulas

S² = P² + Q² — Pythagorean relationship
PF = P / S = cos(θ) — power factor
θ = arccos(PF) = arctan(Q / P) — phase angle

P = S × cos(θ) — real power from apparent and angle
Q = S × sin(θ) — reactive power from apparent and angle
S = V × I — apparent power from voltage and current

P = real power (W, kW) — does useful work. Q = reactive power (VAR, kVAR) — does no work. S = apparent power (VA, kVA) — total delivered by the supply. +Q = inductive (lagging). −Q = capacitive (leading). For the underlying V = IR relationship, see the Ohm’s Law Calculator.

Four Input Modes

Mode 1: P + Q — know real and reactive power. Solves S, PF, θ.
Mode 2: S + PF — know apparent power and power factor. Solves P, Q, θ.
Mode 3: S + Angle — know apparent power and phase angle. Solves P, Q, PF.
Mode 4: V + I + Angle — know voltage, current, and phase angle. Solves S, P, Q, PF.

Induction Motor (S = 5 kVA, PF = 0.85)

Mode 2. A typical induction motor nameplate reads 5 kVA at 0.85 power factor, inductive.

P = 5 × 0.85 = 4.25 kW — real power doing mechanical work
θ = arccos(0.85) = 31.8°
Q = 5 × sin(31.8°) = 5 × 0.527 = 2.63 kVAR — reactive, creates magnetic field

The supply delivers 5 kVA, but only 4.25 kW does useful work. The remaining 2.63 kVAR magnetises the motor’s stator — necessary for operation but it increases current demand without producing output. At 230 V single-phase: I = 5000/230 = 21.7 A. If the power factor were unity, only 18.5 A would be needed for the same mechanical output.

Power Factor Correction (P = 10 kW, Q = 6 kVAR)

Mode 1. A factory load measured at 10 kW real and 6 kVAR reactive (inductive).

S = √(10² + 6²) = √(100 + 36) = √136 = 11.66 kVA
PF = 10 / 11.66 = 0.857
θ = arctan(6/10) = 30.96°

Power factor of 0.857. Most suppliers penalise below 0.90–0.95. To correct to PF = 0.95, the target Q is: Q_target = 10 × tan(arccos(0.95)) = 10 × 0.329 = 3.29 kVAR. The capacitor bank must supply: Q_cap = 6 − 3.29 = 2.71 kVAR of leading reactive power. This reduces apparent power from 11.66 kVA to 10.53 kVA, lowering current by 10% and eliminating the penalty. For the capacitive reactance needed to supply those kVAR, see the Capacitive Reactance Calculator.

Resistive Load (S = 2.4 kVA, θ = 0°)

Mode 3. A heater, kettle, or incandescent bulb — purely resistive.

P = 2.4 × cos(0°) = 2.4 × 1.0 = 2.4 kW
Q = 2.4 × sin(0°) = 0 kVAR
PF = 1.0 (unity)

S = P and Q = 0. All power does useful work. No reactive component, no power factor penalty, no oversized cables needed. This is the ideal case that power factor correction tries to approach. For the energy cost of running this load, use the Electrical Energy Calculator.

Measured V, I, and Angle (230 V, 10 A, 30°)

Mode 4. UK mains, measured with a clamp meter and power analyser.

S = 230 × 10 = 2300 VA = 2.3 kVA
P = 2300 × cos(30°) = 2300 × 0.866 = 1992 W ≈ 2.0 kW
Q = 2300 × sin(30°) = 2300 × 0.5 = 1150 VAR = 1.15 kVAR
PF = 0.866

The supply delivers 2.3 kVA but only 2.0 kW is real. The 1.15 kVAR reactive component means 10 A is flowing, but a resistive load doing the same work would only draw 8.66 A. The difference is reactive current that heats cables and transformers without producing useful output.

Why the Power Triangle Matters

Transformer Sizing

Transformers are rated in kVA (apparent power), not kW. A 100 kVA transformer at PF 0.8 delivers only 80 kW of real power. If your load needs 100 kW at PF 0.8, you need a 125 kVA transformer.

Cable Sizing

Cables carry current. Current is determined by apparent power: I = S/V. A load drawing 10 kW at PF 0.7 requires I = (10/0.7)/230 = 62 A. The same load at PF 0.95 requires only 46 A. Lower power factor means bigger cables, bigger breakers, and more copper cost.

Electricity Bills

Residential customers pay for kWh (real energy). Industrial customers often also pay a reactive power penalty or a maximum demand charge based on kVA. A factory at PF 0.7 pays roughly 43% more in demand charges than at PF 1.0 for the same useful output. To calculate the energy cost itself, use the Power Calculator.

Power Factor Correction

Adding capacitors in parallel with an inductive load supplies the reactive power locally instead of drawing it from the grid. The real power stays the same, but Q drops, S drops, current drops, and the power factor improves.

Power Factor Correction — Step by Step

1. Measure current P and Q (or S and PF)
2. Choose target PF (typically 0.95 or 0.99)
3. Q_target = P × tan(arccos(PF_target))
4. Q_capacitor = Q_current − Q_target
5. Install Q_capacitor kVAR of correction capacitors

Example: P = 50 kW, current PF = 0.75 (Q = 44.1 kVAR). Target PF = 0.95 (Q_target = 16.4 kVAR). Capacitor bank needed: 44.1 − 16.4 = 27.7 kVAR. Apparent power drops from 66.7 kVA to 52.6 kVA — a 21% reduction in current demand.

Frequently Asked Questions

What is power factor?
The ratio of real power to apparent power: PF = P/S = cos(θ). It ranges from 0 to 1. PF = 1 (unity) means all current does useful work. PF = 0.5 means half the current is reactive and does nothing useful. Higher is always better.
What causes poor power factor?
Inductive loads: motors, transformers, fluorescent lighting ballasts, and any device with a coil. The magnetic field stores and returns energy every cycle, creating reactive current. Lightly loaded motors are the worst offenders — a motor at 25% load may have PF = 0.4.
What is the difference between kW, kVA, and kVAR?
kW = real power (does work, turns shafts, produces heat). kVA = apparent power (total delivered by the supply, sizes equipment). kVAR = reactive power (oscillates between source and load, does no work). S² = P² + Q².
Why are transformers rated in kVA instead of kW?
The transformer’s windings and core must carry the total current, which is determined by apparent power. A 100 kVA transformer can deliver 100 kW at unity PF, or 80 kW at PF 0.8. The transformer heats up based on total current regardless of what fraction is real.
Does power factor matter for residential customers?
In most countries, residential meters measure kWh (real energy) only, so there is no direct penalty. However, poor power factor increases current in house wiring, which increases cable heating and voltage drop. In practice, residential PF is usually 0.9+ because most loads are near-resistive.
What power factor do I need?
Most electricity suppliers require 0.90 minimum to avoid penalties. Best practice is 0.95–0.99. Unity (1.0) is ideal but rarely achievable with motors. Over-correction (capacitive leading PF) can cause resonance problems and voltage rise — do not overshoot.

Last updated: March 2026